The PrimeTest 250+ portable appliance tester is battery powered and handheld to allow for fast and efficient testing with clear PASS/FAIL indication and test result values. It has a comprehensive range of mains and battery powered tests, data storage and label printing features.
– Selectable 250V/500V Insulation test
– Mains leakage testing
– Portable RCD Testing
– Variable Earth Continuity and Leakage pass/fail limits
– Can be used with the Seaward PATMobile App
Using Seaward’s free datalogger program and pressing a single download key allows test result data to be quickly and easily transferred from the PrimeTest 250+ to PC at the press of a button. Data is downloaded in a simple CSV spreadsheet format for your PAT records or alternatively the CSV data can be imported directly into Seaward’s PATGuard 3 software for more enhanced record keeping, reporting and certification.
Seaward’s unique ‘ZAP’ technology ensures that earth continuity measurements are accurate in situations where other testers struggle to provide reliable measurements, such as measuring through rust, limescale and other surface contamination.
The PrimeTest Series Testers can be used with our free PATMobile App as part of a combined record keeping and reporting solution. The PATMobile App works with the PrimeTest 250+ to enable the input and storage of test records alongside barcode scanning, wireless label printing, photo tagging and mobile reporting.
Built in Britain and used by 1,000’s of organisations every day.
| Earth Continuity | |
|---|---|
| Output Current | 200mA minimum into 2Ω |
| Test Voltage (o/c) | 9VDC nominal |
| Test Duration (Class I Test) | 2s nominal |
| Display Range | 0.01 – 19.99Ω |
| Pass Value (Class I Test) | 0.1Ω/0.2Ω/0.3Ω |
| Equivalent Leakage | |
|---|---|
| Test Voltage | 40V Nominal AC 50Hz Open Circuit |
| Test Duration | 2s |
| Display Range | 0.1 – 19.99mA |
| Pass Value | 0.5 / 3.5 / 5.0mA |
| Protective Conductor Current | |
|---|---|
| Test Voltage | Supply Voltage, max current 13A |
| Test Duration | 120s maximum |
| Display Range | 0.15 – 9.99mA |
| Pass Value | 3.5 / 5.0mA |
| 3 phase leakage current (Requires 3 phase adaptor accessory) | |
|---|---|
| Test Voltage | 3 phase supply voltage |
| Test Duration | Continuous measurement |
| Display Range | 0.10 – 9.99mA |
| Pass Value | 5mA |
| Power Socket Check | |
|---|---|
| Input Voltage Range | 225 – 254VAC max current 13A UK |
| Indicates Configuration of Voltage Potential | Line potential phase to earth. Line potential phase to neutral. Line potential neutral to earth |
| Insulation Resistance | |
|---|---|
| Test Voltage | 250/500VDC @1mA nomina |
| Test Current | < 2mA (s/c) |
| Test Duration (Class I or II) | 2s |
| Display Range | 0.01 – 19.99MΩ |
| Pass Value Class I | 1.0MΩ |
| Pass Value Class II | 2.0MΩ |
| IEC Lead Test | |
|---|---|
| Test Voltage | 5VDC nominal |
| Test Duration | Time for test (2s max) |
| Test | Live / Neutral Checks for o/c, s/c and crossed |
| Touch Current | |
|---|---|
| Test Voltage | Supply voltage, max current 13A |
| Test Duration | 120s maximum |
| Display Range | 0.10 – 5mA |
| Pass Value | 0.5 / 5.0mA |
| RCD Trip Time | |
|---|---|
| RCD Type | Plugtop and fixed installation |
| Test Voltage | Mains supply voltage |
| Test Current | 30/150mA rms sinusoidal |
| Test Current Phase | 0°/180° auto switched on alternate tests |
| Measuring Range | 0 – 500ms |
| Pass Value | 200ms/40ms |
Our expert sales team is ready to assist you with any questions about our products.